Glazed Aluminium Doors

REI 60 WITH TWO LEAVES

Two leaves REI 60 fire rated aluminum glass door in conformity with UNI 9723 consisting of:

  • REI 60 fire rated glass casing made of special steel/aluminum profiles.
  • Heavy steel two-wing hinges welded on to the profile rotate on thrust-bearing cushions and stainless steel pivots.
  • Self-locking lock, to be opened by simple rotation of the handle.
  • ‘Yale’ cylinder in nickel-plated brass.
  • Stainless steel handle mounted on main leaf at 1040 mm above the finished floor level or at 965 mm when combined with Touchbar panic bars.
  • Automatic closing mechanism via overhead doorcloser with scissor arm.
  • Self-locking latch on secondary leaf and visible closing regulator.
  • Rebate sealing and thermo-expansive materials.
  • Fire rated glass composed of extra-clear float panels with thermo-expansive fire proof material interposed.
  • Special finishing with thermoset powder paints.
  • Subframe to be ordered separately, made of hollow galvanized steel profiles with anchors for mortar fixing (60 x 20 x 2 mm).
Dimensions
min. width L = 950 ( L1 = 567 ; L2 = 383)
min. width with panic bar L = 1500 ( L1 >= 750;                       L2 >= 600)
max. width with or without panic bar L = 2600 ( L1=1300;L2 = 1300)
min. height allowed H = 1809
min. height for escape routes H = 2065
max. height allowed H = 2400
NOTE
With L1 main leaf less than 700 mm or with L2 secondary leaf less than 580 mm, the door closers are on the non-hinge side and prevent opening beyond 110°.For size’s reasons, the SR390 closing regulator (included) can’t be used in combination with the CP2 door closers. Use the RC2 system.
Net passage with 90° opening
with 2 EXUS panic bars L = 524 mm
with 2 TOUCHBAR panic bars L = 422 mm
without panic bars L = 274 mm
Data table REI 60
casing thickness 70 mm
door weight 80 kg/m2
approx. glass thickness 23 mm

ONE-LEAVED REI 60

One leaf REI 60 fire-rated aluminum glazed doors in conformity with UNI 9723 and consisting of:

  • REI 60 fire-rated glazed casing made of special steel/aluminum profiles.
  • Heavy steel three-wing hinges screwed on to the profile rotate on thrust-bearing cushions and stainless steel pivots.
  • Self-locking lock, to be opened by simple rotation of the handle.
  • ‘Yale’ cylinder in nickel-plated brass.
  • Stainless steel handle mounted on main leaf at 1040 mm above the finished floor level or at 965 mm when combined with Touchbar panic bars.
  • Automatic closing mechanism via overhead doorcloser with scissor arm.
  • Rebate sealing and thermo-expansive materials.
  • Fire rated glass composed of extra-clear float panels with thermo-expansive fire proof material interposed.
  • Special finishing with thermoset powder paints.
  • Subframe to be ordered separately, made of hollow galvanized steel profiles with anchors for mortar fixing (60 x 20 x 2 mm).
Dimensions
minimum width L =   630
minimum width with panic bar L =   650
maximum width with or without panic bar L = 1400
minimum height allowed H = 1809
minimum height for escape routes H = 2065
maximum height allowed H = 2400
Net passage with 90° opening
with EXUS panic bar L = 327 mm
with TOUCHBAR panic bar L = 276 mm
without panic bar L = 202 mm
Data table REI 60
casing thickness 70 mm
door weight 80 kg/m2
approx. glass thickness 23 mm

REI 60 WITH FIXED ELEMENTS

REI 60 fire rated complex glazed panel in conformity with UNI 9723 in aluminium, consisting of:

  • REI 60 fire rated glass casing made of special steel/aluminum profiles.
  • Heavy steel three-wing hinges screwed on to the profile rotate on thrust-bearing cushions and stainless steel pivots
  • Self-locking lock, to be opened by simple rotation of the handle.
  • ‘Yale’ cylinder in nickel-plated brass.
  • Stainless steel handle mounted on main leaf at 1040 mm above the finished floor level or at 965 mm when combined with panic bars.
  • Automatic closing mechanism via overhead doorcloser with scissor arm.
  • Self-locking latch on secondary leaf and visible closing regulator.
  • Rebate sealing and thermo-expansive materials.
  • Fire resistant glass consisting of extra-clear float panels with thermo-expansive fire proof material interposed.
  • Special finishing with thermoset powder paints.
  • Subframe to be ordered separately, made of hollow galvanized steel profiles with anchors for mortar fixing (60 x 20 x 2 mm).
Dimensions
min. width   L = 950 ( a = 567;                   p = 383)
min. width with panic bar  L = 1500 ( a >=750;                 p >= 600)
max. width with or without panic bar  L = 2600 ( a =1300;                 p =1300)
min. leaf height allowed H1 = 1809
min. leaf height for escape routes H1 = 2085
max. leaf height allowed H1 = 2400
L2, L3 and H2 measurements min. 300
recommended maximum (others on request) L = 6000; H = 4000;           area=18 m2
Net passage with 90° opening
with 2 EXUS panic bars L1 = 564 mm
with 2 TOUCHBAR panic bars L1 = 462 mm
without panic bars L1 = 314 mm
Data table REI 60
casing thickness 70 mm
door weight 80 kg/m2
approx. glass thickness 23 mm
NOTE
With L1 main leaf less than 700 mm or with L2 secondary leaf less than 580 mm, the door closers are on the non-hinge side and prevent opening beyond 110°.
For purposes of handling, transport and installation plus the risk of breaking the glass, the manufacturer reserves the right, on a case by case basis, to execute fixed glazed doors with the necessary number of panels. The transverse and/or upright dividers inside each glass door are invoiced as separate items. The glass for the fixed parts requires assembly. Wall opening dimensions may vary as a function of lateral and/or upper fixtures and their width and/or height. For size’s reasons, the SR390 closing regulator (included) can’t be used in combination with the CP2 door closers. Use the RC2 system. Any telescopic joints that might be required to reduce size requirements for transport and on-site maneuvering shall be invoiced as separate items (maximum possible size without junctions is 2500 x 3000 mm).

REI 60 ALUMINUM INSTALLATIONS

REI 60 fire rated glass closures made of aluminum are made to measure, which means that all dimensions need to be specified in the order. It is also important that the sections they are applied to be support walls so that the installation can be completed with the necessary cover strips.

 

Installation (1): mounting on external rebate

 

Installation (2): mounting onto block frame

 

Application (3): mounting on internal rebate

 

ONE-LEAVED REI 90 AND REI 120

REI 90 and REI 120, fire rated complex glazed panels in conformity with UNI 9723 in aluminium, consisting of:

  • REI 90 or REI 120 fire rated glass casing made of special steel/aluminum profiles.
  • Heavy steel three-wing hinges screwed on to the profile rotate on thrust-bearing cushions and stainless steel pivots
  • Self-locking lock, to be opened by simple rotation of the handle.
  • ‘Yale’ cylinder in nickel-plated brass.
  • Stainless steel handle mounted at 1040 mm above the finished floor level or at 965 mm when combined with Touchbar panic bars.
  • Automatic closing mechanism via overhead doorcloser with scissor arm.
  • Rebate sealing and thermo-expansive materials.
  • Fire resistant glass consisting of extra-clear float panels with thermo-expansive fire proof material interposed.
  • Special finishing with thermoset powder paints.
  • Subframe to be ordered separately, made of hollow galvanized steel profiles with anchors for mortar fixing (80 x 20 x 2 mm).
Dimensions
minimum width L = 630
minimum width with panic bar L = 650
maximum width with or without panic bar L = 1320
minimum height allowed H = 1809
minimum height for escape routes H = 2065
maximum height allowed H = 2200
Net passage with 90° opening
with EXUS panic bar L = 352 mm
with TOUCHBAR panic bar L = 301 mm
without panic bar L = 227 mm
Data table REI 90 REI 120
casing thickness 95 mm 95 mm
door weight 130 kg/m2 140 kg/m2
approx. glass thickness 48 mm 52 mm

ATTENTION

The considerable weight of glazed doors may make them more difficult to use, especially for people with reduced motor capacities (disabled, seniors, in poor health, etc.). It is important to take this factor into consideration while planning the use of this product and/or to always hold the leaves open by means of electromagnets.

 

TWO-LEAVED REI 90 AND REI 120

Two leaf REI 90 and REI 120, fire rated glazed doors, in conformity with UNI 9723 consisting of:

  • REI 90 or REI 120 fire rated glass casing made of special steel/aluminum profiles.
  • Heavy steel three-wing hinges welded onto the profile rotate on thrust-bearing cushions and stainless steel pivots.
  • Self-locking lock, to be opened by simple rotation of the handle.
  • ‘Yale’ cylinder in nickel-plated brass.
  • Stainless steel handle mounted on main leaf at 1040 mm above the finished floor level or at 965 mm when combined with Touchbar panic bars.
  • Automatic closing mechanism via overhead doorcloser with scissor arm.
  • Self-locking latch on secondary leaf and visible closing regulator.
  • Rebate sealing and thermo-expansive materials.
  • Fire rated glass composed of extra-clear float panels with thermo-expansive fire proof material interposed.
  • Special finishing with thermoset powder paints.
  • Subframe to be ordered separately, made of hollow galvanized steel profiles with anchors for mortar fixing (80 x 20 x 2 mm).
Dimensions
min. width         L = 950  ( L1 = 567;                     L2 = 383)
min. width with panic         L = 1600 ( L1>=800;                   L2 >= 700)
max. width with or without panic bar    L = 2400 ( L1=1200; L2=1200)
min. height allowed   H = 1809
min. height for escape routes   H = 2065
max. height allowed   H = 2200
Net passage with 90° opening
with 2 EXUS panic bars L = 574 mm
with 2 TOUCHBAR panic bars L = 472 mm
without panic bars L = 324 mm
Data table REI 90 REI 120
casing thickness 95 mm 95 mm
door weight 130 kg/m2 140 kg/m2
approx. glass thickness 48 mm 52 mm
NOTE
With L1 main leaf less than 700 mm or with L2 secondary leaf less than 580 mm, the door closers are on the non-hinge side and prevent opening beyond 110°. For size’s reasons, the SR390 closing regulator (included) can’t be used in combination with the CP2 door closers. Use the RC2 system.
ATTENTION
The considerable weight of glazed doors may make them more difficult to use, especially for people with reduced motor capacities (disabled, seniors, in poor health, etc.). It is important to take this factor into consideration while planning the use of this product and/or to always hold the leaves open by means of electromagnets.

REI 90 AND REI 120 WITH FIXED ELEMENTS

REI 90 and REI 120 glazed door complex in conformity with UNI 9723 in aluminum consisting of:

  • REI 90 or REI 120 fire rated glass casing made of special steel/aluminum profiles.
  • Heavy steel three-wing hinges welded onto the profile rotate on thrust-bearing cushions and stainless steel pivots.
  • Self-locking lock, to be opened by simple rotation of the handle.
  • ‘Yale’ cylinder in nickel-plated brass.
  • Stainless steel handle mounted on main leaf at 1040 mm above the finished floor level or at 965 mm when combined with Touchbar panic bars.
  • Automatic closing mechanism via overhead doorcloser with scissor arm.
  • Self-locking latch on secondary leaf and visible closing regulator.
  • Rebate sealing and thermo-expansive materials.
  • Fire rated glass composed of extra-clear float panels with thermo-expansive fire proof material interposed.
  • Special finishing with thermoset powder paints.
  • Subframe to be ordered separately, made of galvanized steel tubing with anchors for mortar fixing (80 x 20 x 2 mm).
Dimensions
min. width   L = 950 ( a = 567;                       p = 383)
min. width with panic bar    L = 1600 ( a>800;                       p >= 700)
max. width with or without panic bar    L = 2400 ( a =1200;                     p =1200)
min. leaf height allowed H1 = 1809
min. leaf height for escape routes H1 = 2085
max. leaf height allowed H1 = 2200
L2, L3 and H2 measurements min. 300
recommended maximum (others on request) L = 6000; H = 4000 area=18 m2
Net passage with 90° opening
with 2 EXUS panic bars L1 = 614 mm
with 2 TOUCHBAR panic bars L1 = 512 mm
without panic bars L1 = 364 mm
Data table REI 90 REI 120
casing thickness 95 mm 95 mm
door weight 130 kg/m2 140 kg/m2
approx. glass thickness 48 mm 52 mm
NOTE
With L1 main leaf less than 700 mm or with L2 secondary leaf less than 580 mm, the door closers are on the nonhinge side and prevent opening beyond 110°. For purposes of handling, transport and installation plus the risk of breaking the glass, the manufacturer reserves the right, on a case by case basis, to execute fixed glazed doors with the necessary number of panels. The transverse and/or upright dividers inside each glass door are invoiced as separate items. Price supplements are required for panels with surface areas greater than 1.2 m2. The glass for the fixed parts requires assembly. Any telescopic joints that might be required to reduce size requirements for transport and on-site maneuvering shall be invoiced as separate items (maximum possible size without junctions is 2500 x 3000 mm). For size’s reasons, the SR390 closing regulator (included) can’t be used in combination with the CP2 door closers. Use the RC2 system. For size’s reasons, the SR390 closing regulator (included) can’t be used in combination with the CP2 door closers. Use the RC2 system.

ATTENTION
The considerable weight of glazed doors may make them more difficult to use, especially for people with reduced motor capacities (disabled, seniors, in poor health, etc.). It is important to take this factor into consideration, therefore, while planning the use of this product and/or to always hold the leaves open by means of electromagnets.

REI 90 AND REI 120 ALUMINUM INSTALLATIONS

REI 90 ad REI 120 fire rated glass closures made of aluminum are built to measure, which means that all dimensions need to be specified in the order. It is also important that they be applied to support walls so that the installation can be completed with the necessary cover strips

 

Installation (1): mounting on external rebate

 

Installation (2): mounting onto block frame

 

Application (3): mounting on internal rebate

 

GENERAL NOTES
The use of suitable colors and glasses is required for doors located in areas that are partially exposed to direct sunlight or other heat sources. The casing must not be exposed to atmospheric agents in any case. For special instructions and recommendations regarding fire rated glass, see the “Notices” reported on the last page of the glass door accessories section of the present website.
All rights reserved. No reproduction (partial or total) without prior authorization by Ninz. Ninz reserves the right to modify the product. Installation should be executed by qualified technicians. Modifications may only be made as indicated in the installation instructions. Original NINZ replacement parts must be used for all repair work.