ONE-LEAVED REI 30 AND REI 60
One leaf REI 30 and REI 60 glazed steel fire door in conformity with UNI 9723, consisting of:
- REI 30 or REI 60 fire rated glass casing, consisting of a 1,5 mm thick weight-bearing cold-formed hollow steel profile frame that is internally insulated with asbestos-free inorganic silicate material and provided with grooves for the rebate sealing and thermo-expansive materials.
- Heavy steel three-wing hinges screwed onto the profile rotate on thrust-bearing cushions and stainless steel pivots.
- Self-locking lock, to be opened by simple rotation of the handle.
- ‘Yale’ cylinder in nickel-plated brass.
- Stainless steel handle mounted at 1040 mm above the finished floor level or at 900 mm when combined with Touchbar panic bars.
- Automatic closing mechanism via overhead doorcloser with scissor arm.
- Rebate sealing and thermo-expansive materials.
- Fire rated glass consisting of extra-clear float panels with thermo-expansive fire proof material interposed.
- Special finishing with thermoset powder paints.
- Subframe to be ordered separately, made of hollow galvanized steel profiles with anchors for mortar fixing (38 x 17 x 2 mm).
Dimensions in mm | |
---|---|
minimum width | L = 630 |
minimum width with panic bar | L = 650 |
maximum width with or without panic bar | L = 1400 |
minimum height allowed | H = 1812 |
minimum height for escape routes | H = 2074 |
maximum height allowed | H = 2400 |
Net passage with 90° opening | |
---|---|
with EXUS panic bar | L = 313 mm |
with TOUCHBAR panic bar | L = 262 mm |
without panic bar | L = 188 mm |
Data table | REI 30 | REI 60 | |
---|---|---|---|
casing thickness | 50 mm | 50 mm | |
glass door weight | 45 kg/m2 | 60 kg/m2 | |
approx. glass thickness | 15 mm | 23 mm | |

TWO-LEAVED REI 30 AND REI 60
REI 30 and REI 60 glazed fire door in conformity with UNI 9723 in steel with two leaves, consisting of:
- REI 30 or REI 60 fire rated glass casing, consisting of a 15/10 mm thick weight-bearing cold-formed hollow
steel profile that is internally insulated with asbestosfree inorganic silicate material and provided with
grooves for the rebate sealing and thermo-expansive materials. - Heavy steel three-wing hinges screwed on to the profile rotate on thrust-bearing cushions and stainless
steel pivots. - Self-locking lock, to be opened by simple rotation of the handle.
- ‘Yale’ cylinder in nickel-plated brass.
- Stainless steel handle mounted on main leaf at 1040 mm above the finished floor level or at 900 mm when combined with Touchbar panic bars.
- Automatic closing mechanism via overhead doorcloser with scissor arm.
- Self-locking latch on secondary leaf and visible closing regulator.
- Rebate sealing and thermo-expansive materials.
- Fire resistant glass consisting of extra-clear float panels with thermo-expansive fire proof material interposed.
- Special finishing with thermoset powder paints.
- Subframe to be ordered separately, made of hollow galvanized steel profiles with anchors for mortar fixing (38 x 17 x 2 mm).
Dimensions in mm | |
---|---|
minimum width | L = 950 (L1 = 569; L2 = 381) |
minimum width with panic bar | L = 1200 (L1 >= 600; L2 >= 400) |
maximum width with or without panic bar | L = 2600 (L1 = 1300; L2 = 1300) |
minimum height allowed | H = 1812 |
minimum height for escape routes | H = 2074 |
maximum height allowed | H = 2400 |

Net passage with 90° opening | |
---|---|
with 2 EXUS panic bars | L = 478 mm |
with 2 TOUCHBAR panic bars | L = 376 mm |
without panic bars | L = 228 mm |
Data table | REI 30 | REI 60 | |
---|---|---|---|
casing thickness | 50 mm | 50 mm | |
glass door weight | 45 kg/m2 | 60 kg/m2 | |
approx. glass thickness | 15 mm | 23 mm | |
REI 30 AND REI 60 WITH FIXED ELEMENTS
REI 30 and REI 60 fire rated complex glazed panel in conformity with UNI 9723 in steel, consisting of:
- REI 30 or REI 60 fire rated glass casing made of a 15/10 mm thick weight-bearing cold-formed hollow steel profiles that are internally insulated with asbestosfree inorganic silicate material and provided with channels for the rebate sealing and thermo-expansive materials.
- Heavy steel three-wing hinges screwed onto the profile rotate on thrust-bearing cushions and stainless steel pivots
- Self-locking lock, to be opened by simple rotation of the handle.
- ‘Yale’ cylinder in nickel-plated brass.
- Stainless steel handle mounted on main leaf at 1040 mm above the finished floor level or at 900 mm when combined with Touchbar panic bars.
- Automatic closing mechanism via overhead doorcloser with scissor arm.
- Self-locking latch on secondary leaf and visible closing regulator.
- Rebate sealing and thermo-expansive materials.
- Fire resistant glass consisting of extra-clear float panels with thermo-expansive fire proof material interposed.
- Special finishing with thermoset powder paints.
- Subframe to be ordered separately, made of hollow galvanized steel profiles with anchors for mortar fixing (38 x 17 x 2 mm).
Dimensions | |
---|---|
min. width | L = 950 ( a = 569; p = 381) |
min. width with panic bar | L = 1200 ( a >=600; p >= 400) |
max. width with or without panic bar | L = 2600 ( a = 1300; p = 1300) |
min. leaf height allowed | H1 = 1812 |
min. leaf height for escape routes | H1 = 2070 |
max. leaf height allowed | H1 = 2400 |
L2, L3 and H2 measurements | min. 300 |
recommended maximum (others on request) | L = 6000; H= 4000; area=18 m2 |
Net passage with 90° opening | |
---|---|
with 2 EXUS panic bars | L1 = 470 mm |
with 2 TOUCHBAR panic bars | L1 = 368 mm |
without panic bars | L1 = 220 mm |
Data table | REI 30 | REI 60 | |
---|---|---|---|
casing thickness | 50 mm | 50 mm | |
glass door weight | 45 kg/m2 | 60 kg/m2 | |
approx. glass thickness | 15 mm | 23 mm | |


NOTE
With L1 main leaf less than 700 mm or with L2 secondary leaf less than 580 mm, the door closers are on the non-hinge side and prevent opening beyond 110°.For purposes of handling, transport and installation plus the risk of breaking the glass, the manufacturer reserves the right, on a case by case basis, to execute fixed glazed doors with the necessary number of panels.The transverse and/or upright dividers inside each glass door are invoiced as separate items. The glass for the fixed parts requires assembly.Wall opening dimensions may vary as a function of lateral and/or upper fixtures and their width and/or height.For size’s reasons, the SR390 closing regulator (included) can’t be used in combination with the CP2 door closers. Use the RC2 system.Any telescopic joints that might be required to reduce size requirements for transport and on-site maneuvering shall be invoiced as separate items (maximum possible size without junctions is 2500 x 3000 mm).
With L1 main leaf less than 700 mm or with L2 secondary leaf less than 580 mm, the door closers are on the non-hinge side and prevent opening beyond 110°.For purposes of handling, transport and installation plus the risk of breaking the glass, the manufacturer reserves the right, on a case by case basis, to execute fixed glazed doors with the necessary number of panels.The transverse and/or upright dividers inside each glass door are invoiced as separate items. The glass for the fixed parts requires assembly.Wall opening dimensions may vary as a function of lateral and/or upper fixtures and their width and/or height.For size’s reasons, the SR390 closing regulator (included) can’t be used in combination with the CP2 door closers. Use the RC2 system.Any telescopic joints that might be required to reduce size requirements for transport and on-site maneuvering shall be invoiced as separate items (maximum possible size without junctions is 2500 x 3000 mm).
STEEL REI 30 AND REI 60 INSTALLATIONS
REI 30 and REI 60 fire rated glass closures are custom built which means that the required dimensions must be specified in the order. It is also important that the sections they are applied to consist of weight bearing walls.
Installation (1): mounting on external rebate

Application (2): mounting onto block frame

Application (3): mounting on internal rebate

GENERAL NOTES
The use of suitable colors and glasses is required for doors located in areas that are partially exposed to direct sunlight or other heat sources. The casing must not be exposed to atmospheric agents in any case. For special instructions and recommendations regarding fire rated glass, see the “Notices” reported on the last page of the glass door accessories section of the present website.
The use of suitable colors and glasses is required for doors located in areas that are partially exposed to direct sunlight or other heat sources. The casing must not be exposed to atmospheric agents in any case. For special instructions and recommendations regarding fire rated glass, see the “Notices” reported on the last page of the glass door accessories section of the present website.
All rights reserved. No reproduction (partial or total) without prior authorization
by Ninz.
Ninz reserves the right to modify the product. Installation should be executed by qualified technicians. Modifications may only be made as indicated in the installation instructions.
Original NINZ replacement parts must be used for all repair work.
by Ninz.
Ninz reserves the right to modify the product. Installation should be executed by qualified technicians. Modifications may only be made as indicated in the installation instructions.
Original NINZ replacement parts must be used for all repair work.